Product Name:DKJ-510BYM Explosion Proof Electrical Integration Actuator
Product Type:DKJ-510BM
torque :1600 NM
force: N
whole stroke :
power:
220V 380V 415V
control method:
input signal:
output signal:
Relative introduction:
DKJ-510BYM Explosion Proof Electrical Integration Actuator, output torque is 1600Nm, domestic manufactured actuator
First, use
DKJ-B-type rotary electric actuator is DDZ electric unit in the instrument cluster execution unit, which accepts adjusting unit (or computer) signal, automatically adjusting the steering actuator to complete the task, widely used in power plants, chemical, petroleum, metallurgy, building materials, heating, light industry, water treatment and other industries. It can output torque and 90-degree angle.
DKJ-B electric actuators with explosion-proof structure, explosion-proof grade dⅡBT3, you can use (use of reference GB3836 · 1-2000 "explosive environment with explosion-proof electrical equipment General requirements") stipulated in explosive environments.
DKJ electric actuator, with a variety of electric operator can adjust the system to complete the "Manual ← → Auto" switch without disturbance, in a timely manner to be adjusted manually distant objects.
I produced the actuator position transmitter are using the latest sensing element, the circuit reference to the latest foreign company, set power transformer, rectifier, regulator, amplifier, constant current one, made of modules (M) so that the actuator reliability and stability, making the system more secure.
Second, the main technical performance
1, the output signal: type Ⅱ 0-10mA, DC; Ⅲ type 4-20mA, DC; Input signal: switch signal
2 input channels: three
3, the input resistance: type Ⅱ 200Ω; Ⅲ type 250Ω
4, the output torque: see table
5, the output shaft 100 ± 20 times per revolution Miao
6, the output shaft angle 90o effective
7 Dead: Type Ⅱ ≤150μA; Ⅲ type ≤240μA
8, the damping characteristics: no shock
9, the basic error: ± 2.5%
10, hysteresis: 1.5%
11, the power supply voltage: 220V (+ 22V, -33V) 50Hz
12, use of the environment:
(1) Ambient temperature: Amplifiers: 0 ~ + 50 ℃; actuators: -25 ~ + 55 ℃
(2) Relative humidity: Amplifiers: 10% to 70%, Actuator: ≤95%
(3) Allow the air capacity booster containing explosive gas is not higher than Class Ⅱ grade B T3 group, but does not contain corrosive gases.